Figure 6.38 - Diagram for the torque master/slave function
- F > Fx _ 1: This function activates the relay and/or transistorized outputs
set to this option when the output frequency value (F) is greater than the
value set at P369 (Fx) plus the hysteresis value set at P370. When F <
Fx - P370, the outputs set to this option are deactivated (refer to figure
6.39 t)).
- F > Fx _ 2: With this option the hysteresis for the acceleration is
disabled, therefore, this function activates the relay and/or transistorized
outputs set to this option when the output frequency value (F) is greater
than the value set at P369 (Fx). When F < Fx - P370, the outputs set to
this option are deactivated (refer to figure 6.39 v)).
- Set point = Process Variable. This function activates the digital or
relay output when the Set point value equals the Process Variable value
(refer to figure 6.39 v)).
- No E32 - It indicates that the inverter is disabled due to an E32 error.
- Ready 2 - Indicates that the motor is disabled (motor stopped) without
error and without undervoltage.
Symbols used in the Digital Output functions:
N = P002 (Motor speed)
N* = P001 (Frequency Reference)
Nx = P288 (Speed Nx) - User selected speed reference point.
Ny = P289 (Speed Ny) - User selected speed reference point.
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
XC4:6
COM
XC4:4
DGND
XC4:8
R 500 
24 Vcc
3 W
XC4:5
XC1:17, 18
AO1
XC1:19, 20
AO2
M
Slave
XC1:10
GND
CFW-09
XC1:2
DI2 (FWD/REV)
XC1:12, 13
AI1 (Speed Reference)
XC1:15, 16
AI2 (Max. Torque
Current)
EBA.01
M
185

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents