Parameters Description
These parameters can be useful for counting the number of monthly or weekly hours that the system is
operating and the kWh generated.
Once parameter P1014 or P1015 is reset, parameter P1059 returns to value "0" automatically.

5.5 HMI MONITORING

This parameter group allows the user to configure which parameters will be shown on the HMI display in the
monitoring mode.
P0205 – Read Parameter Selection 1
P0206 – Read Parameter Selection 2
P0207 – Read Parameter Selection 3
P0208 – Reference Scale Factor
P0209 – Reference Engineering Unit 1
P0210 – Reference Engineering Unit 2
P0211 – Reference Engineering Unit 3
P0212 – Reference Decimal Place
NOTE!
Refer to the CFW11 frequency inverter programming manual for further information about the HMI
parameters.

5.6 READING PARAMETERS

P1010 – Solar Pump Drive Application Version
Adjustable
0.00 to 10.00
Range:
Properties:
RO
Access groups via HMI:
Description:
This parameter indicates the version of the ladder application software developed for the Solar Pump Drive.
P1011 – Current Tracking Setpoint
Adjustable
0 to 1000 V
Range:
Properties:
RO
Access groups via HMI:
Description:
This parameter shows the current value of the DC voltage setpoint that will be modified by the system in search
of the maximum reference point.
P1012 – Actual Pressure Setpoint / Speed
Adjustable
0.0 to 300.0 psi/bar/Hz
Range:
Properties:
RO
Access groups via HMI:
Description:
This parameter displays the current value of the control setpoint in function of the system configuration:
SPLC
SPLC
SPLC
Application Default Setting:
Application Default Setting:
Application Default Setting:
Solar Pump Drive | 31
-
-
-