WEG CFW-09 User Manual page 288

Frequency inverter
Hide thumbs Also See for CFW-09:
Table of Contents

Advertisement

LED
Color
Link
Green
Module Status
Green or Red
Network Status
Green or Red
Activity
Green
CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
Configuration of the Network Master Data
For the master configuration, besides the IP address used by the EtherNet/IP
board, it is necessary to indicate the number of I/O instances and the quantity of
data exchanged with the master in each instance. For the CFW-09 with Anybus-S
EtherNet/IP board, the following values must be programmed:
Input Instance: 100
Output Instance: 150
Data amount programmable through P309: it may be 2, 4 or 6 words with 16
bits (4, 8 or 12 bytes).
The EtherNet/IP board for the CFW-09 is described in the network as a Generic
Ethernet Module. By using these configurations it is possible to program the
network master so that it communicates with the inverter.
Indication
The communication board has four two-color LEDs located on the right bottom
corner to indicate the module and the network status.
Link
Activity
Figure 8.46 - Indication LEDs for the status of the EtherNet/IP network
On: the module is connected to another device on the network (typically a hub or
switch).
Off: the module is not connected to another device.
Steady Off: No power applied o the module.
Steady Green: The module is operating correctly.
Flashing Green: the module has not been configured.
Flashing Red: A minor recoverable error has been detected.
Steady Red: A major internal error has been detected.
Flashing Green/Red: The module is performing a power on self-test.
Steady Off: The module has no power or no IP address has been assigned.
Steady On: the module has at least one established EtherNet/IP connection.
Flashing Green: There are no EtherNet/IP connections established to the module.
Flashing Red: One or more of the connections in which this module is the target has
timed out.
Steady Red: The module has detected that its IP address is already in use.
Flashing Green/Red: The module is performing a power on self-test.
Flashing: indicates that a packet has been received and/or transmitted.
Module
1
2
Status
Network
4
3
Status
Function
289

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents