[Factory Setting]
Parameter
P287
Hysteresis for Nx/Ny
(2) (11)
P288
Nx Speed
(2) (11)
P289
Ny Speed
P290
(7)
0.0 to 2.0 x P295
Ix Current
0.1 A(< 100)-1A(> 99.9)
P291
Zero Speed Zone
P292
N = N* Band
(At Speed Band)
P293
Tx Torque
P294
Hours Hx
Range
Unit
Description / Notes
0.0 to 5.0
Used by the Digital and Relay Outputs functions:
[ 1.0 ]
N > Nx and N < Ny.
0.1 %
0 to P134
Used by the Digital and Relay Outputs functions:
[ 120 (100) ]
N* > Nx, N > Nx and N < Ny.
1 rpm
0 to P134
[ 1800 (1500) ]
1 rpm
Used by the Digital and Relay Outputs functions:
[ 1.0 x P295 ]
Is > Ix and Is < Ix.
Used by the Digital and Relay Outputs function Zero Speed and the
1 to 100
Zero Speed Disable (Refer to P211 and P212).
[ 1 ]
1 %
Used by the Digital and Relay Outputs function N = N* (At Speed).
1 to 100
[ 1 ]
1 %
Used by the Digital and Relay Outputs functions Torque > Tx and
0 to 200
Torque < Tx. In this output mode, the motor torque indicated in
[ 100 ]
parameter P009 is compared with the value programmed in P293.
1 %
The setting is expressed in % of the motor rated current (P401 = 100 %)
0 to 6553
Used in the functions of the digital outputs Hours Enabled higher than
[ 4320 ]
Hx.
1 h
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
193