Pre-Power Checks; Initial Power-Up - WEG CFW-09 User Manual

Frequency inverter
Hide thumbs Also See for CFW-09:
Table of Contents

Advertisement

5.1 PRE-POWER
CHECKS
5.2 INITIAL
POWER-UP
START-UP
This chapter provides the following information:
How to check and prepare the inverter before power-up;
How to power-up and check for proper operation;
How to operate the inverter.
The inverter shall be installed according to chapter 3: Installation and Connection.
DANGER!
Disconnect the AC input power before making any connections. Even when the
inverter project is different from the suggested connections, the following
recommendations are applicable.
1) Check all connections
Check if the power, grounding and control connections are correct and
well tightened.
2) Clean the inside of the inverter
Remove all shipping material from the inside of the inverter or cabinet.
3) Check if the selected inverter AC power is correct (refer to item 3.2.3)
4) Check the motor
Check all motor connections and verify if its voltage, current and frequency
match the inverter specifications.
NOTES!
Operation in VT mode
When the motor data is set properly during the first power-up routine,
the inverter automatically sets the additional parameters used for
the correct operation under this control mode.
5) Uncouple the load from the motor
If the motor cannot be uncoupled, make sure that the direction of rotation
(FWD/REV) cannot cause damage to the machine.
6) Close the inverter cover or cabinet doors
After the inverter has been checked, AC power can be applied:
1) Check the supply voltage
Measure the line voltage and check if it is within the specified range (refer to
item 9.1).
2) Power-up the AC input
Close the input circuit breaker or disconnect switch.
3) Check if the power-up has been successful
When the inverter is powered up for the first time or when the factory default
parameter values are loaded (P204 = 5), a start-up sub-routine is run. This
sub-routine requests the user to program some basic parameters to ensure
proper operation and motor protection.
A start-up programming example is shown below:
Inverter
Line: CFW-09
Rated Current: 9 A
Rated Voltage: 380 V to 480 V
Model: CFW090009T3848ESZ
Cooling: Self-ventilated
5
CHAPTER
Motor
WEG IP55
Power: 5 hp
rpm: 1730, 4 POLE
Rated Current: 7.9 A
Rated Voltage: 460 V
Frequency: 60 Hz
Cooling: Self-ventilated
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents