[Factory Setting]
Parameter
P221
(1)
LOCAL Speed
Reference Selection
P222
(1)
REMOTE Speed
Reference Selection
Range
Unit
Description / Notes
P220
0
1
2
3
4
5
6
7
8
9
10
In the factory default setting, the key
Local or Remote Mode. When powered up, the inverter starts in Local
Mode.
The description AI1' as apposed to AI1 refers to the analogue signal after
0 to 11
scaling and/or gain calculations have been applied to it (Refer to figure
[ 0 ]
6.29).
-
P221/P222
0 to 11
0
1
[ 1 ]
-
2
3
4
5
6
7
8
9
10
11
The reference value set by the
P121.
Details of the Electronic Potentiometer (E.P.) operation in figure 6.37m).
When option 7 (E.P.) is selected, program P265 or P267 = 5 and P266 or
P268 = 5.
When option 8 is selected, program P266 and/or P267 and/or P268 to 7.
When P203 = 1 (PID), do not use the reference via E.P. (P221/P222 = 7).
When P203 = 1 (PID), the value programmed in P221/P222 becomes the
PID setpoint.
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
LOCAL/REMOTE Selection
Always LOCAL Mode
Always REMOTE mode
Key
of the Keypad (HMI) (LOCAL Default)
Key
of the Keypad (HMI) (REMOTE Default)
Digital inputs DI2 to DI8 (P264 to P270)
Serial (Local Default) - SuperDrive or incorporated Modbus
Serial (Remote Default) - SuperDrive or incorporated Modbus
Fieldbus (Local Default) - Optional Fieldbus board
Fieldbus (Remote Default) - Optional Fieldbus board
PLC (L) - Optional PLC board
PLC (R) - Optional PLC board
Table 6.25 - LOCAL/REMOTE selection
LOCAL/REMOTE Speed Reference Selection
and
Analog Input AI1' (P234/P235/P236)
Analog Input AI2' (P237/P238/P239/P240)
Analog Input AI3' (P241/P242/P243/P244)
Analog Input AI4' (P245/P246/P247)
Sum of the Analog Inputs AI1' + AI2' > 0 (Negative values are zeroed)
Sum of the Analog Inputs AI1' + AI2'
Electronic Potentiometer (E.P.)
Multispeed (P124 to P131)
Table 6.26 - LOCAL/REMOTE speed reference selection
and
of the Keypad (HMI) will select
of the keypad
Serial
Fieldbus
PLC
keys is contained in parameter
155