CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
Figure 8.48 - Control and monitoring window when accessing the CFW-09 through the WEB
NOTE!
It is necessary to have a PC with an EtherNet card connected to the same network
of the CFW-09 and a WEB browser (MS Internet Explorer or Mozilla/Firefox.
Configurations
Follow the steps below to operate the CFW-09 in an EtherNet/IP network.
1)
Install the KFB-EN kit into the CFW-09 variable frequency inverter.
2)
At parameter P309 select the EtherNet/IP protocol and the number of input/
output words, P309 = 7, 8 or 9.
3)
Connect the RJ-45 plug of the EtherNet cable to the inverter and make sure
that the Link LED is ON (LED 1).
4)
Open your WEB browser and type the inverter address on the network. The
factory default value is 'http://192.168.0.1'. Make sure that JavaScript and
cookies are enabled in the WEB browser.
The data access is protected by username and password. The CFW-09 has
the following factory default values: Username: web Password: web