NOTE!
The last frequency reference value set via the
If you wish to change this value before enabling the inverter, change parameter
P121 (Keypad Reference).
OBSERVATIONS:
(1) If the rotation direction of the motor is not correct, switch off the inverter.
Wait 10 minutes to allow a complete discharge of the capacitors and then
swap any two wires at the motor output.
(2) If the acceleration current becomes too high, specially at low frequencies
(< 15 Hz), adjust the Torque Boost at P136.
Increase/decrease the content of P136 gradually until you obtain an
operation with constant current over the entire frequency range.
Refer to P136 in chapter 6.
(3) If E01 fault occurs during deceleration, increase the deceleration time at
P101 / P103.
CHAPTER 5 - START-UP
DESCRIPTION
Motor decelerates down to 0 rpm
Motor accelerates from 0 rpm up to
the JOG speed set at P122
Ex.: P122 = 150 rpm
CCW direction of rotation
Motor decelerates down to 0 rpm
and
keys is saved.