1.2 Basic Configuration

1.2.1 Basic configuration
The following devices are required to operate the inverter. Proper peripheral devices must be selected and correct
connections made to ensure proper operation. Incorrect system configuration and connections can cause the
inverter to operate improperly, its life to be reduced considerably, and in the worst case, the inverter to be
damaged.
Please handle the inverter properly in accordance with the information in each section as well as the precautions
and instructions of this manual. (For connections of the peripheral devices, refer to the corresponding manuals.)
(NFB)
or
(ELB)
(MC)
AC reactor
(MT-BAL)
Ground
DC reactor
Ground
Name
Use the power supply within the
Power supply
permissible power supply specifications of
the inverter.
Earth leakage
The breaker should be selected with care
circuit breaker
since a large inrush current flows in the
(ELB) or no-fuse
inverter at power on. (Refer to page 26.)
breaker (NFB)
The magnetic contactor need not be
provided. When installed, do not use it to
Magnetic
start or stop the inverter. It might reduce the
contactor
inverter life.
(Refer to page 26.)
The reactors must be used when the
power factor is to be improved or the
inverter is installed near a large power
Reactors
supply system (1000KVA or more and
wiring distance within 10m). Make selection
carefully.
• The inverter life is influenced by ambient
temperature. The ambient temperature
should be as low as possible within the
permissible range.
This must be noted especially when the
inverter is installed in an enclosure.
Inverter
(Refer to page 6.)
• Incorrect wiring might lead to inverter
damage. The control signal lines should
be kept away from the main circuit to
protect them from noise.
(Refer to page 8.)
Devices
Do not connect a power capacitor, surge
connected to the
suppressor or radio noise filter to the output
output
side.
To prevent an electric shock, always
Ground
ground the motor and inverter.
2
OUTLINE
Description
1