YASKAWA iC9200 Series Operating Manual page 38

Hide thumbs Also See for iC9200 Series:
Table of Contents

Advertisement

Basics and mounting
Wiring > Wiring System SLIO periphery
Data
Wiring proceeding
38
CAUTION
Danger of injury from electrical shock and damage to the CPU respectively to
the modules!
Put the iC9200 Series in a safe, powered down state before starting installa-
tion, disassembly or wiring of the iC9200 Series modules!
With wiring the terminal modules, terminals with spring clamp technology are used for
wiring. The spring clamp technology allows quick and easy connection of your signal and
supply lines. In contrast to screw terminal connections this type of connection is vibration
proof.
U
240V AC / 30V DC
max
I
10A
max
Cross section
0.08 ... 1.5mm
Stripping length 10mm
1
Pin no. at the connector
2
Opening for screwdriver
3
Connection hole for wire
1.
Insert a suited screwdriver at an angel into the square opening as shown. Press and
hold the screwdriver in the opposite direction to open the contact spring.
2.
Insert the stripped end of wire into the round opening. You can use wires with a
cross section of 0.08mm
3.
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal.
(AWG 28 ... 16)
2
up to 1.5mm
.
2
2
HB700 | CPU | PMC921xEx | en | 24-04