YASKAWA iC9200 Series Operating Manual page 105

Hide thumbs Also See for iC9200 Series:
Table of Contents

Advertisement

iC9200 Series
System variable
EC_SLAVE_STATE
EC_SLAVE_LAST_AL_STATUS_CODE
1) Index 0 is reserved. The 1. EtherCAT slave is assigned to Index 1.
PROFINET
system variables optional
PROFINET system variables - PROFINET controller functionality
System variable
PNIO_SYSTEM_BF
PNIO_SYSTEM_SF
PNIO_MAINTENANCE_DEMANDED
PNIO_MAINTENANCE_REQUIRED
HB700 | CPU | PMC921xEx | en | 24-04
System variables and status information > System variables
Description
ARRAY[0...512] OF BYTE
Returns all states of the EtherCAT slaves connected to
the EtherCAT master:
00h: The state is unknown.
01h: INIT
02h: PreOp
03: BootStrap
04h: SafeOp
08h: OP
ARRAY[0...512] OF WORD
Returns last read AL Status Codes of the EtherCAT
slaves connected to the EtherCAT master.
Please note that a separate licence is required for the use of PROFINET,
which must be activated accordingly!
Type - description
BOOL - Missing connection to a configured PROFINET device.
An error has occurred in the PROFINET network, i.e. no
connection could be established to at least one configured
PROFINET device.
This value is not set if the "Control BF" parameter on a
PROFINET device was set to FALSE. The PROFINET device
was thus removed from the connection monitoring.
BOOL - Diagnostic interrupt on a configured PROFINET device.
At least one PROFINET device reports a system error as a
diagnostic interrupt or maintenance alarm.
The error priority can be found in the variables
PNIO_DIAG_AVAILABLE, PNIO_MAINTENANCE_DEMANDED
and PNIO_MAINTENANCE_REQUIRED.
BOOL - maintenance demand
At least one PROFINET device reports a "maintenance
demand" - maintenance alarm with high priority when the con-
nection is active.
The PROFINET device can be identified by means of the
RALRM diagnostic block.
BOOL - maintenance required
At least one PROFINET device reports a "maintenance
required" - maintenance alarm with low priority when the con-
nection is active.
The PROFINET device can be identified by means of the RALRM
diagnostic block.
Deployment CPU iC921xM-EC
- slave states
1)
1)
- Slave AL Status codes
105