Basics and mounting

Mounting

16x periphery module
2.4
Mounting
30
76.5
WARNING
Unintentional machine start-up
Do not mount or dismount when the power is on!
Disconnect the CPU from the power supply before mounting or dis-
mounting and secure the power supply against being switched on again!
Do not switch on the power supply until the system has been completely
mounted. Pay attention to the diagnostic indicators and any diagnostic
messages.
The machine/plant may only be started when no hazard can result from
the machine/plant.
NOTICE
Electronic damage due to insufficient external fuse protection - No safe
release in the event of a fault
Insufficient external fusing will cause electronic damage to the CPU.
Fuse the supply voltage externally according to the connected load
(number of System SLIO F participants/sum of current consumption of
each participant).
Ensure safe triggering of the external fuse.
If you use a melting fuse, the power supply unit must be able to supply
four times the rated current of the melting fuse. This ensures safe trig-
gering in the event of an error.
NOTICE
Damage due to improper handling
Handle the CPU and components with care!
When installing the CPU and components, ensure that mechanical
damage is avoided!
Note on mounting
Mount the CPU in a closed control cabinet or control box with degree
of protection IP54 or higher on a 35 mm standard mounting rail.
Use a mounting rail according to EN 60715.
12.9
15
HB700 | CPU | PMC921xEx | en | 24-04