Standard wiring
Fusing
State of the electronic power
supply via LEDs
2.5.2.2
Wiring 8x periphery modules
Terminal module terminals
HB700 | CPU | PMC921xEx | en | 24-04
DC24V
(1) DC 24V supply CPU:
DC 5V electronic section supply I/O area (max. 2A)
(2) Power module 007-1AB00:
DC 24V power section supply (max. 10A)
(3) DC 5V electronic section supply I/O area
(4) DC 24V power section supply I/O area
CAUTION
Since the power section supply is not internally protected, it is to be exter-
nally protected with a fuse, which corresponds to the maximum current. This
means max. 10A is to be protected by a 10A fuse (fast) respectively by a line
circuit breaker 10A characteristics Z!
The power section supply is to be externally protected with a fuse, which corresponds
to the maximum current. This means max. 10A is to be protected with a 10A fuse
(fast) respectively by a line circuit breaker 10A characteristics Z!
It is recommended to externally protect the electronic power section supply for CPU
an I/O area with a 2A fuse (fast) respectively by a line circuit breaker 2A characteris-
tics Z.
After PowerON the RUN respectively MF LED at every System SLIO module is on, so
far as the sum current does not exceed the maximum value. With the CPU this is 3A. If
the total current exceeds the maximum value, the LEDs are no longer triggered. Here the
power module with the order number 007-1AB10 is to be placed between the periphery
modules.
CAUTION
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description, haz-
ardous voltages are not allowed to be connected to the corresponding ter-
minal module!
2
1
DC24V
0V
0V
Basics and mounting
Wiring > Wiring System SLIO periphery
3
SysDC5V
DC 24V
4
...
37