Basics and mounting

General data for iC9200 Series

2.9
General data for iC9200 Series
Conformity and approval
Conformity
CE
Approval
UL
Others
RoHS
Protection of persons and device protection
Type of protection
Electrical isolation
to the field bus
to the process level
Insulation resistance
Insulation voltage to reference earth
Inputs / outputs
Protective measures
Environmental conditions to EN 61131-2
Climatic
Storage / transport
Operation
Horizontal installation hanging
Horizontal installation lying
Vertical installation
Air humidity
Pollution
Installation altitude max.
Mechanical
Oscillation
Shock
Mounting conditions
Mounting place
Mounting position
56
2014/30/EU
EMC directive
UL 61010-2-201
UL is in preparation
2011/65/EU
Directive on the restriction of the use of certain haz-
ardous substances in electrical and electronic equipment
-
IP20
-
electrically isolated
-
electrically isolated
EN 61010-2-201
-
-
AC / DC 50V, test voltage AC 500V
-
against short circuit
EN 60068-2-14
-40...+85°C
EN 61131-2
0...+60°C
EN 61131-2
0...+55°C
EN 61131-2
0...+40°C
EN 60068-2-30
RH1 (without condensation, rel. humidity 10...95%)
EN 61131-2
Degree of pollution 2
-
2000m
EN 60068-2-6
1g, 9...150Hz
EN 60068-2-27
15g, 11ms
-
Control cabinet or switch box of protection class IP54 or
higher on a 35 mm standard mounting rail.
-
Horizontal and vertical
⮫ 'Assembly possibilities'...page 32