Recommended Fuse Ratings For Ul Installation - Danfoss D9h Operating Manual

Enclosed drives
Table of Contents

Advertisement

VLT® AutomationDrive FC 302
Operating Guide
Model
Fuse P/N
N250
Mersen NH3GG69V425
N315
Mersen NH3GG69V500
N355
Mersen NH3GG69V500
N400
Mersen NH4GG69V630
N500
Mersen NH4GG69V800
N560
Mersen NH4GG69V800
N630
ABB OFAA4AM1000
N710
ABB OFAA4AM1000

5.9.3 Recommended Fuse Ratings for UL Installation

The fuses and MCCBs contained in the enclosed drive are suitable for both short circuit and branch circuit protection. Use only these
fuses.
UL Approval is valid for maximum input voltage of 600 V. Per UL508A, the short-circuit current rating (SCCR) is as follows:
Enclosed drives with a fusible disconnect or fusible disconnect and contactor option have 65 kA SCCR at the rated voltage.
Enclosed drives with single switchgear (mains contactor only or non-fusible disconnect only option) have a 5 kA SCCR, but can
reach 65 kA if the recommended Class fuses are used upstream.
Enclosed drives with the MCCB option have a 65 kA interrupting rating for 380–480 V. For 525–690 V, the interrupting rating is
30 kA for the N315 model and 50 kA for the others.
The table values are calculated using correction factors for a 40 °C (104 °F) ambient operating condition and using cables with a
minimum insulation rating of 90 °C (194 °F).
Table 71: Recommended Fuse Ratings for UL Installation, 380–500 V
Drive model
Fuse P/N (Mersen)
N90K
A4J300
N110
A4J350
N132
A4J400
N160
A4J500
N200
A4J600
N250
AABY750
N315
A4BY800
N355
A4BY1000
N400
A4BY1000
N450
A4BY1100
N500
A4BY1200
Danfoss A/S © 2021.10
Fuse size
Rated cur-
rent [A]
3
425
3
500
3
500
4
630
4
800
4
800
4
1000
4
1000
Fuse P/N (Danfoss)
Maximum cur-
rent [A]
70CPE10965
300
70CPE10966
350
70CPE10522
400
70CPE10968
500
70CPE10523
600
70CPE10969
750
70CPE10974
800
70CPE10975
1000
70CPE10975
1000
70CPE10976
1100
70CPE10977
1200
Minimum pro-
Maximum fuse
spective SC cur-
rating F1 [A]
rent of the grid
[kA]
9.5
425
12
500
12
500
14
630
19
800
19
800
25
1000
25
1000
Maximum fuse
rating F1 [A]
300
350
400
500
600
750
800
1000
1000
1100
1200
AQ262139143212en-000301 / 130R0879 | 109
Electrical Installation
Minimum volt-
Type F1
age rating [V]
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
aM
690
aM
Minimum volt-
Class F1
age rating [V]
500
Class J
500
Class J
500
Class J
500
Class J
500
Class J
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L

Advertisement