Wiring Configuration: Run/Stop - Danfoss D9h Operating Manual

Enclosed drives
Table of Contents

Advertisement

VLT® AutomationDrive FC 302
Operating Guide
Table 82: Wiring Configuration for Analog Voltage Feedback Transducer (4-wire)
XD2.10
+24 V
+24 V
XD2.11
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
XD2.17
D IN
D IN
XD2.19
+10 V
XD2.6
+
A IN
XD2.7
A IN
XD2.8
COM
XD2.9
A OUT
XD2.5
-
COM
XD2.4
0-10 V
U - I
A54

8.1.6 Wiring Configuration: Run/Stop

Table 83: Wiring Configuration for Run/Stop Command with External Interlock
+24 V
XD2.10
XD2.11
+24 V
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17
D IN
XD2.19
Danfoss A/S © 2021.10
Parameters
Function
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-21 Terminal 54 High Voltage
Parameter 6-24 Terminal 54 Low Ref./Feedb. value
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 54 in the parameter title corresponds to terminal XD2.8 in the control compartment.
Parameters
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Wiring Configuration Examples
Setting
0.07 V*
10 V*
0*
50*
Setting
[8] Start*
[7] External interlock
AQ262139143212en-000301 / 130R0879 | 127