4.5.4 Potentially Explosive Atmospheres
EXPLOSIVE ATMOSPHERE
Installing the drive in a potentially explosive atmosphere can lead to death, personal injury, or property damage.
-
Install the unit in a cabinet outside of the potentially explosive area.
-
Use a motor with an appropriate ATEX protection class.
-
Install a PTC temperature sensor to monitor the motor temperature.
-
Install short motor cables.
-
Use sine-wave output filters when shielded motor cables are not used.
As required by the EU Directive 2014/34/EU, any electrical or electronic device intended for use in an environment with a potentially
explosive mixture of air, flammable gas, or dust must be ATEX-certified. Systems operated in this environment must fulfill the fol-
lowing special conditions to comply with the ATEX protection class:
•
Class d specifies that if a spark occurs, it is contained in a protected area.
•
Class e prohibits any occurrence of a spark.
Motors with class d protection
Does not require approval. Special wiring and containment are required.
Motors with class e or class n protection
When combined with an ATEX-approved PTC monitoring device like the VLT
need an individual approval from an approbated organization.
Motors with class d/e protection
The motor itself has an e ignition protection class, while the motor cabling and connection environment are in compliance with the
d classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output.
MOTOR THERMISTOR SENSOR MONITORING
Units with the VLT® PTC Thermistor Card MCB 112 option are PTB-certified for potentially explosive atmospheres.
4.6 Installation Requirements
OVERHEATING
Improper mounting can result in overheating and reduced performance.
-
Install the drive according to the installation and cooling requirements.
•
Locate the unit as near to the motor as possible. For the maximum motor cable length, see
•
Ensure unit stability by mounting the unit to a solid surface.
•
Ensure that the strength of the mounting location supports the unit weight.
•
Ensure that there is enough space around the unit for proper cooling. Refer to
•
Ensure enough access to open the door.
•
Ensure cable entry from the bottom.
Danfoss A/S © 2021.10
W A R N I N G
PTC Thermistor Card MCB 112, installation does not
®
N O T I C E
N O T I C E
Mechanical Installation
10.5 Motor and Control
10.10 Enclosure
Airflow.
AQ262139143212en-000301 / 130R0879 | 41
Cables.
Need help?
Do you have a question about the D9h and is the answer not in the manual?
Questions and answers