Potentially Explosive Atmospheres; Installation Requirements - Danfoss D9h Operating Manual

Enclosed drives
Table of Contents

Advertisement

VLT® AutomationDrive FC 302
Operating Guide

4.5.4 Potentially Explosive Atmospheres

EXPLOSIVE ATMOSPHERE
Installing the drive in a potentially explosive atmosphere can lead to death, personal injury, or property damage.
-
Install the unit in a cabinet outside of the potentially explosive area.
-
Use a motor with an appropriate ATEX protection class.
-
Install a PTC temperature sensor to monitor the motor temperature.
-
Install short motor cables.
-
Use sine-wave output filters when shielded motor cables are not used.
As required by the EU Directive 2014/34/EU, any electrical or electronic device intended for use in an environment with a potentially
explosive mixture of air, flammable gas, or dust must be ATEX-certified. Systems operated in this environment must fulfill the fol-
lowing special conditions to comply with the ATEX protection class:
Class d specifies that if a spark occurs, it is contained in a protected area.
Class e prohibits any occurrence of a spark.
Motors with class d protection
Does not require approval. Special wiring and containment are required.
Motors with class e or class n protection
When combined with an ATEX-approved PTC monitoring device like the VLT
need an individual approval from an approbated organization.
Motors with class d/e protection
The motor itself has an e ignition protection class, while the motor cabling and connection environment are in compliance with the
d classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output.
MOTOR THERMISTOR SENSOR MONITORING
Units with the VLT® PTC Thermistor Card MCB 112 option are PTB-certified for potentially explosive atmospheres.

4.6 Installation Requirements

OVERHEATING
Improper mounting can result in overheating and reduced performance.
-
Install the drive according to the installation and cooling requirements.
Locate the unit as near to the motor as possible. For the maximum motor cable length, see
Ensure unit stability by mounting the unit to a solid surface.
Ensure that the strength of the mounting location supports the unit weight.
Ensure that there is enough space around the unit for proper cooling. Refer to
Ensure enough access to open the door.
Ensure cable entry from the bottom.
Danfoss A/S © 2021.10
W A R N I N G
PTC Thermistor Card MCB 112, installation does not
®
N O T I C E
N O T I C E
Mechanical Installation
10.5 Motor and Control
10.10 Enclosure
Airflow.
AQ262139143212en-000301 / 130R0879 | 41