10.7 Filter Specifications
10.7.1 Passive Harmonic Filter Specifications
Phase imbalance
Voltage variation
Nominal frequency
Overload capability
Maximum inrush current, drive side
Maximum inrush current, PHF input side
Power derating
Table 109: Displacement Power Factor (Cos Phi)
Load [%]
Automatic capacitor control [p.u.]
10
1.000
25
-0.830
50
-0.996
75
0.997
100
0.986
160
0.980
Positive numbers indicate lagging reactive currents. Negative numbers indicate leading currents.
1
The capacitor connecting contactor switches at 20% load.
2
10.7.2 Line Reactor Specifications
All line reactors are equipped with thermal switches and are looped to the enclosed drive for overtemperature protection. For more
details, refer to the Control Compartment section. The line reactor configuration varies depending on the enclosure and voltage re-
quired.
Table 110: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 380–500 V
Enclosure
D9h
D9h
D9h
D10h
D10h
D10h
E5h
E5h
E5h
E6h
E6h
Danfoss A/S © 2021.10
Capacitor always connected [p.u.]
(1)(2)
-0.790
-0.830
-0.996
0.997
0.986
0.980
Model
N90K
N110
N132
N160
N200
N250
N315
N355
N400
N450
N500
-2%, +2% (of 50 Hz or 60 Hz) when PHF is installed
150% for 60 s in a period of 10 minutes
Capacitor always open [p.u.]
(1)
1.000
0.990
0.950
0.930
0.920
0.910
Impedance [%]
2.70
3.22
2.87
3.47
3.01
3.65
3.30
3.62
3.83
2.94
3.23
AQ262139143212en-000301 / 130R0879 | 177
Specifications
Maximum of 3%
+10%–15%
Maximum 5xI
nom drive
Maximum 2xI
nom drive
Same as drive
(1)