Danfoss D9h Operating Manual page 164

Enclosed drives
Table of Contents

Advertisement

VLT® AutomationDrive FC 302
Operating Guide
FC 302
Intermittent (60 s overload) (at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 500 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Maximum number and size of cables per phase
2
- Mains [mm
(AWG)]
- Mains with disconnect [mm
- Mains with fusible disconnect [mm
- Mains with contactor [mm
2
- Motor [mm
(AWG)]
Drive module power loss at 400 V [W]
Drive module power loss at 460 V [W]
Drive efficiency
(2)
Output frequency [Hz]
(4)
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
PHF overtemperature trip [°C (°F)]
Line reactor overtemperature trip [°C (°F)]
dU/dt filter overtemperature trip [°C (°F)]
Sine-wave filter overtemperature trip [°C (°F)]
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
1
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
2
cy class, see the Ambient Conditions section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
See also Input Power Option Losses section.
3
If using an output filter, the output frequency is limited further. See
4
Table 104: Electrical Data, Mains Supply 3x380–500 V AC
FC 302
High/normal overload
164 | Danfoss A/S © 2021.10
2
(AWG)]
2
(AWG)]
2
(AWG)]
(1)(2)(3)
(1)(2)(3)
N315
810
649
416
456
430
470
468
511
578
634
520
569
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
6178
6928
5322
5910
0.98
0–590
110 (230)
80 (176)
145 (293)
150 (302)
150 (302)
150 (302)
10.3.1 Motor Output (U, V,
W).
Specifications
N355
N400
885
746
1017
456
516
482
470
540
540
511
587
587
634
718
670
569
653
653
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
4x127 (4x250 mcm)
6851
8036
7297
5846
6933
7240
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
145 (293)
145 (293)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
N450
N500
HO
NO
HO
AQ262139143212en-000301 / 130R0879
803
554
582
632
771
704
8783
7969
NO

Advertisement

Table of Contents
loading