Troubleshooting - Danfoss D9h Operating Manual

Enclosed drives
Table of Contents

Advertisement

VLT® AutomationDrive FC 302
Operating Guide
9.4.101 ALARM 427, FPC Supply
Cause
Supply voltage fault (5 V, 24 V, or 48 V) on fan power card is detected.

Troubleshooting

Check fan power card wiring.
Replace fan power card.
9.5 Troubleshooting
Table 100: Troubleshooting
Symptom
Possible cause
Display dark/No
Missing input power.
function
Missing or open fuses.
No power to the LCP.
Short circuit on control volt-
age (terminal 12 or 50) or at
control terminals.
Incompatible LCP (LCP from
VLT
2800 or
®
5000/6000/8000/ FCD or
FCM).
Wrong contrast setting.
Display (LCP) is defective.
Internal voltage supply fault
or SMPS is defective.
Intermittent dis-
Overloaded supply (SMPS)
play
due to improper control wir-
ing or a fault within the AC
drive.
Motor not run-
Service switch open or miss-
ning
ing motor connection.
No mains power with 24 V DC
option card.
LCP stop.
Missing start signal (Standby).
Motor coast signal active
(Coasting).
Wrong reference signal
source.
158 | Danfoss A/S © 2021.10
Test
Check for loose connections.
See Open power fuses in this table
for possible causes.
Check the LCP cable for proper
connection or damage.
Check the 24 V control voltage sup-
ply for terminal 12/13 to 20–39, or
10 V supply for terminals 50–55.
Test using a different LCP.
To rule out a problem in the con-
trol wiring, disconnect all control
wiring by removing the terminal
blocks.
Check reference signal:
Maintenance, Diagnostics, and
Troubleshooting
Solution
Check the input power source.
Follow the recommendations provi-
ded.
Replace the faulty LCP or connection
cable.
Wire the terminals properly.
Use only LCP 101 (P/N 130B1124) or
LCP 102 (P/N. 130B1107).
To adjust the contrast, press [Status] +
[▲]/[▼].
Replace the faulty LCP or connection
cable.
Contact supplier.
If the display stays lit, the problem is in
the control wiring. Check the wiring
for shorts or incorrect connections. If
the display continues to cut out, fol-
low the procedure for Display dark\No
function.
Connect the motor and check the
service switch.
Apply mains power.
Depending on the operating mode,
press [Auto On] or [Hand On].
Apply a valid start signal.
Apply 24 V on terminal 27 or program
this terminal to [0] No operation.
Program correct settings. Check pa-
rameter 3-13 Reference Site. Set preset
reference active in parameter group
AQ262139143212en-000301 / 130R0879