Installation; Sto Installation For Frequency Converters With Functional Safety Group 1 (Sto - Not Upgradable) - Danfoss iC7 Series Operating Manual

Frequency converters, 1.3–106 a
Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

iC7 Series Functional Safety
Operating Guide

4 Installation

4.1 STO Installation for Frequency Converters with Functional Safety Group 1 (STO - Not Upgrada-
ble)
For motor connection, AC mains connection, and control wiring, follow the instructions for safe installation in the documentation
shipped with the drive. All functional safety related wiring must be done on terminal blocks X31 and X32. See
location of the terminals.
If multi-stranded wires are used in the installation, ferrules or other suitable means must be used to prevent a single core from
short-circuiting with adjacent pins. Install the drive in a cabinet rated IP54 or higher as per IEC 60529, or in an equivalent environ-
ment.
Illustration 5: Functional Safety Terminals
Table 5: Functional Safety I/O Terminals in Frequency Converters
Terminal X31
Numbering
Terminal Name
41
24 V
42
S.INA+
43
S.INB+
44
S.FB+
12 | Danfoss A/S © 2023.03
N O T I C E
Functions
+ 24 V DC Output
+ STO Input Channel A
+ STO Input Channel B
+ STO Input Channel B
41 42 43 44
X31
45
46 47 48
X32
Terminal X32
Numbering
Terminal Name
45
GND
46
S.INA–
47
S.INB–
48
S.FB–
Installation
Illustration 5
for the
Functions
0 V/GND
- STO Input Channel A
- STO Input Channel B
- STO Feedback
AQ319741840653en-000201 / 136R0268