Nortel Meridian 1 Succession 1000M Installation And Configuration Manual page 251

Small system
Hide thumbs Also See for Meridian 1 Succession 1000M:
Table of Contents

Advertisement

Installing and connecting cross-connect terminals
4
Replace the retaining bar when you have connected all the cables to the
cabinet.
5
Terminate all the 25-pair cables installed at the cross-connect terminal.
Label all the cables at the cross-connect terminal blocks according to the
card slot allocation plan.
6
Install the AUX cable on the lower 9-pin connector located on the left side
of the connector area in the lower part of each cabinet.
Terminate the AUX cable at the cross connector located on the left side
of the connector. See Figure 102 on
Table 27
AUX cable terminations for the Cabinet system
Color
Wire number
W-BL
1
BL-W
2
O-W
3
W-O
4
G-W
5
W-G
6
*Each AUX cable can provide power for only one console.
Procedure 40
Connecting the cables for the Chassis system
1
Loosen the Velcro straps at each connector you plan to use.
2
Connect a 25-pair cable to each of the connectors that will contain a line
or trunk card. Refer to the card slot assignment plan.
Make sure you tag both ends of each cable with the chassis and
connector numbers. See Figure 102 on
page
250.
Designation
BRTN
BRTN
-48V AUX (250mA)
PFTS
-15V AUX
+15V AUX
page
Small System
Installation and Configuration
Page 251 of 562
Connection
to QUA6-J1 1R
to QUA6-J1 2R
to QUA6-J1 25T, 25R
to QUA6-J1 2T
Console power*
Console power*
250.

Advertisement