Confirming The Installation And Wiring; Items To Confirm When Installation And Wiring Are Completed - Mitsubishi Electric MELSEC-Q Series User Manual

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

4.4 Confirming the installation and wiring

4.4.1 Items to confirm when installation and wiring are completed

Important
If the Simple Motion module is faulty, or when the required signals such as the proximity dog signal and
forced stop signal are not recognized, unexpected accidents such as "not decelerating at the proximity
dog during machine HPR and colliding with the stopper", or "not being able to stop with the forced stop
signal" may occur. Execute a checking wiring of external input signal. The connection confirmation by
positioning test function must be carried out not only when structuring the positioning system, but also
when the system has been changed with module replacement or rewiring, etc.
Check the following points when completed with the installation of Simple Motion
module and wiring.
Is the module correctly wired?
The following four points are confirmed using the positioning test function of
GX Works2.
With this function, "whether the direction that the Simple Motion module recognizes as
forward run matches the address increment direction in the actual positioning work",
and "whether the Simple Motion module recognizes the external input signals such as
the manual pulse generator and forced stop", etc., can be checked.
Are the Simple Motion module and servo amplifier correctly connected?
Are the servo amplifier and servomotor correctly connected?
Are the Simple Motion module and external devices (input signals) correctly
connected?
Are the servo amplifier and external wiring (FLS, RLS and DOG) correctly
connected?
Refer to the "Simple Motion Module Setting Tool Help" of GX Works2 for details of
"Positioning test function".
Note that the monitor data of the "[Md.30] External input signal" in the GX Works2 may
also be used to "confirm the connection between the Simple Motion module and
external devices (input signals)".
Chapter 4 Installation, Wiring and Maintenance of the Product
4 - 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qd77gf4Melsec-qd77gf8Melsec-qd77gf16

Table of Contents