Mitsubishi Electric MELSEC-Q Series User Manual page 524

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Setting item
[Da.1] Operation pattern
[Da.2] Control method
[Da.3] Acceleration time No.
[Da.4] Deceleration time No.
Positioning address/
[Da.6]
movement amount
[Da.7] Arc address
[Da.8] Command speed
Dwell time/JUMP
[Da.9]
destination positioning
data No.
M code/Condition
data No./Number of
[Da.10]
LOOP to LEND
repetitions
Axis to be interpolated
[Da.20]
No.1
Axis to be interpolated
[Da.21]
No.2
Axis to be interpolated
[Da.22]
No.3
(Note): Refer to Section 5.3 "List of positioning data" for information on the setting details.
(2) Set JUMP instruction to positioning data No. that "continuous positioning
control" or "continuous path control" is set in operation pattern.
It cannot set to positioning data No. that "positioning complete" is set in
operation pattern.
(3) Positioning control such as loops cannot be executed by conditional JUMP
instructions alone until the conditions have been established.
When loop control is executed using JUMP instruction, an axis operation
status is "analyzing" during loop control, and the positioning data analysis
(start) for other axes are not executed. As the target of the JUMP instruction,
specify a positioning data that is controlled by other than JUMP and NOP
instructions.
Positioning data setting example
[When "JUMP instruction" is set in positioning data No. 1 of axis 1]
Setting example
JUMP instruction
500
1
Chapter 9 Major Positioning Control
Setting not required. (Setting value is ignored.)
Set the JUMP instruction.
Setting not required. (Setting value is ignored.)
Set the positioning data No. 1 to 600 for the JUMP
destination. (The positioning data No. of the JUMP
instruction cannot be set. Setting its own positioning data No.
will result in the error "Illegal data No." (error code: 502).)
Set the JUMP instruction execution conditions with the
condition data No.
0
: Unconditional JUMP
1 to 10 : Condition data No.
("Simultaneous start" condition data cannot be
set.)
Setting not required (setting value is ignored).
9 - 124