Mitsubishi Electric MELSEC-Q Series User Manual page 779

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Related buffer memory address
10+150n
11+150n
12+150n
13+150n
14+150n
15+150n
17+150n
18+150n
19+150n
20+150n
21+150n
22+150n
23+150n
Set range
(Setting with sequence program)
<Speed limit value>
1 to 1000000000 [PLS/s]
-2
1 to 2000000000 [ 10
mm/min or others]
1 to 8388608
1 to 8388608
[Pr.11]×[Pr.2]
0 ≤
[Pr.3]×[Pr.4] ≤ 4194303
• [mm] [inch] [PLS]
–2147483648 to 2147483647
• [degree] 0 to 35999999
• [mm] [inch] [PLS]
–2147483648 to 2147483647
• [degree] 0 to 35999999
0, 1
0, 1
16 - 33
Chapter 16 Troubleshooting
Remedy
• Set a value which is not less than the HPR speed.
• With the setting brought into the setting range, turn the PLC
READY signal [Y0] from OFF to ON.
With the setting brought into the setting range, turn the PLC
READY signal [Y0] from OFF to ON.
"[Pr.2] Number of pulses per rotation (AP)",
"[Pr.3] Movement amount per rotation (AL)",
"[Pr.4] Unit magnification (AM)"
"[Pr.11] Backlash compensation amount"
Review the items above.
(Refer to Section 5.2.1 or Section 5.2.3)
• Bring the setting into the setting range.
• In a unit other than degree, set so that the lower limit value is
smaller than the upper limit value.
• Bring the setting into the setting range.
• In the unit of "degree", set "0: Apply software stroke limit on
feed current value".
With the setting brought into the setting range, turn the PLC
READY signal [Y0] from OFF to ON.
n: Axis No.-1