Mitsubishi Electric MELSEC-Q Series User Manual page 76

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Main functions
Block start (Normal start)
Condition start
Wait start
Simultaneous start
Repeated start (FOR loop)
Repeated start (FOR
condition)
Multiple axes simultaneous
start control
JOG operation
Inching operation
Manual pulse generator
operation
Speed-torque control
Synchronous control
[Da.1] Operation pattern
Independent positioning control
(positioning complete)
Continuous positioning control
Continuous path control
With one start, executes the positioning data in a random block with the
set order.
Carries out condition judgment set in the "condition data" for the
designated positioning data, and then executes the "block start data".
When the condition is established, the "block start data" is executed.
When not established, that "block start data" is ignored, and the next
point's "block start data" is executed.
Carries out condition judgment set in the "condition data" for the
designated positioning data, and then executes the "block start data".
When the condition is established, the "block start data" is executed.
When not established, stops the control until the condition is
established. (Waits.)
Simultaneously executes the designated positioning data of the axis
designated with the "condition data". (Outputs commands at the same
timing.)
Repeats the program from the block start data set with the "FOR loop" to
the block start data set in "NEXT" for the designated number of times.
Repeats the program from the block start data set with the "FOR
condition" to the block start data set in "NEXT" until the conditions set in
the "condition data" are established.
Starts the operation of multiple axes simultaneously according to the
command output level.
(Positioning start No. 9004, same as the "simultaneous start" above)
Outputs a command to servo amplifier while the JOG start signal is ON.
Outputs commands corresponding to minute movement amount by
manual operation to servo amplifier.
(Performs fine adjustment with the JOG start signal.)
Outputs pulses commanded with the manual pulse generator to servo
amplifier.
Carries out the speed control or torque control that does not include the
position loop for the command to servo amplifier by switching control
mode.
Carries out the synchronous control that synchronizes with input axis by
setting the system such as gear, shaft, change gear and cam to the
"synchronous control parameter".
In "major positioning control" ("high-level positioning control"), "Operation pattern" can
be set to designate whether to continue executing positioning data. Outlines of the
"operation patterns" are given below.
When "independent positioning control" is set for the operation pattern of
the started positioning data, only the designated positioning data will be
executed, and then the positioning will end.
When "continuous positioning control" is set for the operation pattern of
the started positioning data, after the designated positioning data is
executed, the program will stop once, and then the next following
positioning data will be executed.
When "continuous path control" is set for the operation pattern of the
started positioning data, the designated positioning data will be
executed, and then without decelerating, the next following positioning
data will be executed.
Chapter 3 Specifications and Functions
Details
Details
3 - 8
Reference
section
10.3.2
10.3.3
10.3.4
10.3.5
10.3.6
10.3.7
10.5
11.2
11.3
11.4
12.1
12.2
Reference
section
9.1.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-qd77gf4Melsec-qd77gf8Melsec-qd77gf16

Table of Contents