External Dimensions and Part Names

Input module and output modules
74
19.7
2
3
1
4
4
3
Left side
5
All dimensions are in "mm".
a
FX5-C16EYR/D-TS: X = 30.7 mm
FX5-C32Eä/ä-TS: X = 20.1 mm
No.
Description
1
Extension connector for next module
m Powered
2
POWER LED
é Not powered or hardware error
m Input/output is ON
3
Indicator LED
é Input/output is OFF
4
Terminal for input or output signals
5
Extension connector for preceding module
m: LED is ON, é: LED is OFF
Input/output modules
19.7
74
a
X
Left side
7
All dimensions are in "mm".
No.
Description
1
Extension connector for next module
m Powered
2
POWER LED
é Not powered or hardware error
m Input is ON
Indicator LEDs for
3
inputs
é Input is OFF
4
Terminal for input signals
5
Terminal for output signals
m Output is ON
Indicator LEDs for
6
outputs
é Output is OFF
7
Extension connector for preceding module
m: LED is ON, é: LED is OFF

Installation and Wiring

20.1
P
2
m Make sure to cut off all phases of the power supply externally before
3
attempting installation or wiring work.
1
4
Failure to do so may cause electric shock or damage to the product.
m Use the product within the general environment specifications described
in the User's Manual (Hardware) of the CPU module used.
Never use the product in areas with excessive dust, oily smoke, con-
5
ductive dusts, corrosive gas (salt air, Cl
gas, vibration or impacts, or expose it to high temperature, condensa-
tion, or rain and wind.
6
If the product is used in such conditions, electric shock, fire, malfunc-
tions, deterioration or damage may occur.
E
m Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
m When drilling screw holes or wiring, make sure cutting or wire debris
does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
m Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC
board, thereby causing nonconformities.
m Install the product securely using a DIN rail.
m Connect the input/output cables securely to their designated connectors.
Loose connections may cause malfunctions.
m Turn off the power to the PLC before attaching or detaching the follow-
ing devices. Failure to do so may cause device failures or malfunctions.
– Peripheral devices, expansion board, and expansion adapter
– Extension modules, bus conversion module, and battery
Mounting
The spring clamp terminal type I/O modules of the MELSEC FX5 series can be
mounted on a DIN rail.
Preparation for installation
Connect the extension modules described in this manual to other modules
before mounting these modules on a DIN rail.
The procedure for connecting a module (extension connector type) is shown
with an example of how to connect an I/O module to a FX5UC CPU module.
a Slide the hook for coupling the exten-
sion module ("A" in the right figure) of
the existing module (right side).
b Remove the extension connector
cover for subsequent modules ("B"
in the right figure).
c Connect the extension module as shown in the figure below.
d Slide the hook for coupling the extension module ("A" in the figure below)
of the existing module to fix the extension module ("C" in the figure below).
d
A
DIN rail mounting
The procedure for installing a module to a DIN rail is shown with an example
of how to install an I/O module (extension cable type).
DANGER
a Push out the DIN rail mounting hook
(Right fig. "A").
, H
S, SO
or NO
), flammable
2
2
2
2
b Fit the upper edge of the DIN rail
mounting groove (Right fig. "B")
onto the DIN rail.
CAUTION
c Lock the DIN rail mounting hook
while pressing the module against
the DIN rail.
Wiring
P
m Caused by a damaged output module an output may not be set cor-
rectly. Design external circuits and mechanisms to ensure safe opera-
tions of the machine in such a case.
m An external power supply failure or a malfunction of the PLC may
result in undefined conditions. Provide a safety circuit on the outside
of the PLC (i. e. emergency stop circuit, a protection circuit, interlock
circuit etc.) to ensure safety.
E
m Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to malfunction of the PLC
caused by abnormal data written to the PLC due to the effects of noise.
– Do not bundle AC supply lines together with DC supply lines.
– Do not lay signal cables close to the main circuit, high-voltage power
A
lines, or load lines. Otherwise effects of noise or surge induction are
likely to take place. Keep a safe distance of more than 100 mm from
the above when wiring.
B
m The temperature rating of the cable should be 80 °C or more.
m Observe the following items when wiring a spring clamp terminal block.
Ignorance of the this items may cause electric shock, equipment failures,
short circuit, disconnection, malfunction, or damage of the product.
– The disposal size of the cable end should follow the dimensions
described in this manual.
– Twist the end of stranded wires and make sure there are no loose wires.
– Do not solder-plate the electric wire ends.
– Connect only the electric wires of regulation size.
A
– Fix the electric wires so that the terminal block and connected parts
of electric wires are not directly stressed.
C
A
d
4
c
c
c
a
A
B
c
DANGER
CAUTION