Restrictions
(1) The error "Continuous path control not possible" (error code: 516) will occur
and the operation cannot start if "continuous positioning control" or
"continuous path control" is set in "[Da.1] Operation pattern".
(2) "Position-speed switching control" cannot be set in "[Da.2] Control method" of
the positioning data when "continuous path control" has been set in "[Da.1]
Operation pattern" of the immediately prior positioning data. (For example, if
the operation pattern of positioning data No. 1 is "continuous path control",
"position-speed switching control" cannot be set in positioning data No. 2.) The
error "Continuous path control not possible" (error code: 516) will occur and
the machine will carry out a deceleration stop if this type of setting is carried
out.
(3) The software stroke limit range is only checked during speed control if the "1:
Update feed current value" is set in "[Pr.21] Feed current value during speed
control".
The software stroke limit range is not checked when the control unit is set to
"degree".
(4) The error "Software stroke limit +" (error code: 507) or "Software stroke limit -"
(error code: 508) will occur and the operation cannot start if the start point
address or end point address for position control exceeds the software stroke
limit range.
(5) Deceleration stop will be carried out if the position-speed switching signal is
not input before the machine is moved by a specified movement amount.
When the position-speed switching signal is input during automatic
deceleration by positioning control, acceleration is carried out again to the
command speed to continue speed control.
When the position-speed switching signal is input during deceleration to a stop
with the stop signal, the control is switched to the speed control to stop the
machine.
Restart is carried out by speed control using the restart command.
(6) The warning "Speed limit value over" (warning code: 501) will occur and
control is continued by "[Pr.8] Speed limit value" if a new speed exceeds
"[Pr.8] Speed limit value" at the time of change of the command speed.
(7) If the value set in "[Da.6] Positioning address/movement amount" is negative,
the error "Outside address range" (error code: 530) will occur.
(8) Set WITH mode in "[Pr.18] M code ON signal output timing" at M code use.
The M code will not be output, and the M code ON signal will not turn ON if the
AFTER mode is set.