Checking Concentration Limit - Fujitsu AIRSTAGE J-IIIL Design & Technical Manual

Table of Contents

Advertisement

1-2. Checking concentration limit

Check concentration limit following step 1 and 2, and take appropriate measures depending on the
situation.
1.
Calculate amount of refrigerant per refrigerant system.
Amount of refrigerant
system
Amount of factory
charge
2.
Calculate room volume by regarding portion marked in gray as one room or the smallest room.
(a) Without partition
(c) When there are partitions, but there is an
effective opening for ventilation between the
rooms.
Indoor unit
Smallest room
1-2. Checking concentration limit
Amount of additional
+
refrigerant
Amount of refrigerant
added to system
based on pipe
length, pipe size,
and indoor units
Outdoor unit
Indoor unit
Outdoor unit
Total amount of refrigerant in
=
When one refrigerant system is
divided into 2 or more refrigerant
systems and each system is in-
dependent, total amount of refrig-
erant of each system shall be
(b) When there are partitions, but there is an
effective opening for ventilation between the
rooms.
Opening
Indoor unit
- (09-2) -
Unit: lb (kg)
system
adopted.
Outdoor unit
Partition
1. Refrigerant leakage caution