Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 392

Table of Contents

Advertisement

¢ Specifications
Power source voltage
Power source frequency
Input power
Display
LED indicator
External interface
Usage temperature range
Usage humidity range
Storage temperature range
Storage humidity range
Dimensions
(H × W × D)
Weight
Fuse capacity
 Wiring specifications
Use
Power supply cable
(for stranded wire)
Power supply cable
(for solid wire)
Transmission cable
External input/output
cable
LAN cable
2-5. Central remote controller (UTY-DCGYZ1)
V
Hz
W
°F (°C)
%
°F (°C)
%
in (mm)
oz (g)
A
Cable size
18—16 AWG
60245 IEC 57 or equivalent
2
(0.8—1.25 mm
)
18—14 AWG
2
(0.8—2.0 mm
)
LEVEL4 (NEMA) non-polar 2-
22 AWG
core, twisted pair solid core
2
diameter 0.03 in (0.65 mm),
(0.33 mm
)
22 AWG
Polar 2-core, twisted pair
2
Max cable length: 82 ft (25 m)
(0.33 mm
)
Category 5 or more straight
- (05-54) -
1 Ø AC 100—240
7.0-inch TFT color LCD panel (WVGA)
Power LED (Green)
Transmission line
External input: Either emergency stop, batch
operation/stop, electricity meter
(Either Dry contact or apply voltage can be selected.)
External output: Operation state, error state
Wired LAN (100 BASE-TX)
32 to 104 (0 to 40)
0 to 85 (no condensation)
-4 to 158 (-20 to 70)
0 to 85 (no condensation)
5-5/16 × 8-1/2 × 1-1/2 (134.6 × 216.2 × 37.9)
28.2 (800)
Wire type
1 Ø AC 100—240 V 50/60 Hz,
1 Ø AC 100—240 V 50/60 Hz,
shielded type
Use cable in accordance with
cable
50/60
7
5
Remarks
2-wire + ground
(Always ground the unit)
2-wire + ground
(Always ground the unit)
LonWorks compatible cable
local rules for cable.
100 BASE-TX support
2. Control units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents