Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 610

Table of Contents

Advertisement

• Remote controller address (Set F)
Maximum of 16 indoor units can be controlled by 1 individual remote controller with connecting
remote controller cable.
Those units connected with remote controller cable are regarded as a remote controller group.
Even there is only 1 indoor unit with one or no wired controller is connected, it is regarded as
one remote controller group.
– 3-wire type (Only for manual address setting):
Remote controller address
1
*
: Set the remote controller address in order of 0, 1, 2, ..., 15. (Blank is now allowed.)
2
*
: When remote controller group is not constructed (1:1 connection of indoor unit and re-
mote controller), be sure that the remote controller address is set to the initial setting "0"
(factory setting).
– 2-wire type:
In initial starting up of this unit, addresses will be automatically set. Do not change the re-
mote controller address for the indoor unit. (Keep it at the initial setting "0".)
1-3. Manual address setting method
00
00
00
0
00
01
1
*
R. C. line: 3 wire
3-wire type R. C.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
- (07-10) -
00
02
2
00
03
3
00
04
1
3-wire type R. C.
Rotary switch
RC AD
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
00
05
0
*
2
*
2
Switch position
1. System settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents