Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 716

Table of Contents

Advertisement

¢ DIP switch setting
• SET2-1: Terminal resistance setting
When there is no other terminal resistance in the network segment to which the convertor is
connected, set to "ON".
SET2-1
• SET2-2: Setting prohibited
• SET2-3: Setting prohibited
• SET2-4: Used remote controller setting
Change the DIP switch setting depending on the remote controller model name attached to
the indoor unit.
NOTE: When 2-wire type remote controller is connected, set to "OFF" for all models.
SET2-4
ON
OFF
• SET3: Remote controller 2-wire/3-wire switching
Set this setting so that the configuration match with the setting of the used indoor unit.
Also, set matched with the connection method of the remote controller cable to be connected.
2WIRE
3WIRE
2-17. Network convertor (UTY-VTGX)
ON
OFF
SW1
OFF
ON
SW1
OFF
ON
Wireless remote controller model name:
3-wire type wired remote controller model name:
AR-WAG1E (UTY-RNNGU)
Other than the remote controller mentioned above
SET3
Terminal resistance
Enable
Disable
Fixed at OFF
Setting prohibited
Fixed at OFF
Setting prohibited
AR-RAK1E
Model name
Rear view
YYYYYYYY
Model name
Rear view
RC 2-wire/3-wire
2-wire type
3-wire type
- (07-116) -
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
2. Function settings