2-6. Function summary of outdoor unit external input/output

¢ Outdoor unit external input function
Dry contact/ Apply voltage
Low noise mode operation
Outdoor unit operation peak
Function
Power usage information from
Specifications
When using this function, select appropriate level from the following options:
1
*
:
42-00 Low noise level 1 (lower than rated value)
42-01 Low noise level 2 (lower than level 1)
2
When using this function, select appropriate level from the following options:
*
:
30-00 Energy saving level 1 (Stop)
30-01 Energy saving level 2 (Operated at 40% capacity)
30-02 Energy saving level 3 (Operated at 60% capacity)
30-03 Energy saving level 4 (Operated at 80% capacity)
30-03 Energy saving level 5 (Operated at 100% capacity)
NOTES:
• For selecting relay, minimum permissible load must be less than 1 mA.
• When using Apply voltage, take "+" polarity for Pin 1.
• Number inside bracket such as "(20-00)" in the table above indicates function number and set-
ting number.
• ●: Equipping the function.
¢ Outdoor unit external output function
Dry contact/ Apply voltage
Function
Specifications
External power
NOTES:
• When using Apply voltage, take "+" polarity for Pin 1.
• ●: Equipping the function.
2-6. Function summary of outdoor unit external input/output
Emergency stop
Cooling/Heating priority
control
Batch stop
electricity meter
Terminal
Signal type
Operation status
Error status
Base heater
Terminal
Terminal output voltage
Allowable
voltage
supply
Allowable current
Dry contact DC 12 V
1
● *
CN131
CN132
(Pin1-2)
(Pin1-2)
Edge
Apply voltage
CN136
(Pin1-2)
DC 12—240 V
30 mA or less
- (08-7) -
(20-01)
2
● *
(20-00)
CN133
CN134
CN135
(Pin1-2)
(Pin1-2)
(Pin1-2)
Pulse
Dry contact
CN137
CN115
(Pin1-2)
(Pin1-3)
AC 240 V
1 A or less
2. Outdoor unit