Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 117

Table of Contents

Advertisement

9. Electrical characteristics
Select the breaker based on MCA and MAX.CKT.BKR of the following tables.
Select the wire diameter based on the larger value of MCA or TOCA of the following tables.
Select a wire diameter which withstands the breaker capacity.
Select the correct cable type and size according to the country or region's regulations.
Limited wiring length is in case voltage drop less than 2%. When wiring length extend longer, select
the wiring size of larger diameter.
• RLA: Rated Load Amp of compressor under the standard condition
• MCA: Minimum Circuit Ampacity = Maximum operating current (Full load)
• MSC: Maximum Starting Current
• TOCA: Total Over-Current Ampacity
• MAX.CKT.BKR: Maximum Circuit Breaker
• GFEB: Ground Fault Equipment Breaker
9-1. Stand-alone
Ton
Model name
6
AOU72RLAVL
8
AOU96RLAVL
10
AOU120RLAVL
Ton
Model name
6
AOU72RLAVL
8
AOU96RLAVL
10
AOU120RLAVL
9-1. Stand-alone
Power supply: 60 Hz, 208/230 V
MCA (A)
38
39
47
Wiring
Compressor
specifications
MAX.CKT.BKR
RLA (A)
(A)
40
26.1
40
27.5
50
33.5
- (03-21) -
Full load characteristics
TOCA (A)
40
40
50
Outdoor fan motor
Output (kW)
375 × 2
375 × 2
375 × 2
MSC (A)
30.6
31.6
38.0
GFEB
FLA (A)
0.8 + 0.8
100 mA,
1.4 + 0.9
0.1 sec or less
1.6 + 1.6
9. Electrical characteristics