Indoor unit connection check
Address setting
Refrigerant piping connection
(Outdoor unit)
Leak pressure test
Vacuum evacuation and drying
Additional refrigerant charge
Gas leakage check
Outside panel installation
Test run and adjustment
End of work
Hand over
Customer training
2-1. Important items when using refrigerant (R410A)
Calculate additional refrigerant charge. Add additional re-
frigerant with R410A gage manifold and hose.
Pressurize system with 609 psi (4.2 MPa) nitrogen
System must hold 600 psi for a minimum of 24
hours.
Do not purge system with refrigerant.
Use a vacuum pump with check valve to prevent the
back flow of vacuum pump oil into the refrigerant
system.
- (06-16) -
2. Piping design