Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 813

Table of Contents

Advertisement

• TM201 (CN412): Apply voltage terminal
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal TM201 (CN412).
Connection exampla1: When the switch is connected
Connection exampla2: When the electricity meter is connected
1
Make the power supply DC12 to 24 V. Select a power supply capacity with an ample sur-
*
:
plus for the connected load.
2
Do not impress a voltage exceeding 24 V across K1-K2.
*
:
3
The allowable current is DC 10 mA or less. (Recommended: DC 5 mA)
*
:
Provide a load resistance such that the current becomes DC10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
A twisted pair cable 22 AWG (0.33 mm
[25 m])
4-1. Touch panel controller
1
*
DC power supply
12 to 24 V
3
*
2
*
3
*
1
*
DC power supply
12 to 24 V
2
*
PCB
TM201
PCB
TM201
2
) should be used. (Maximum cable length: 82 ft
- (08-59) -
PCB
PCB
4. Controller