Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 30

Table of Contents

Advertisement

Calculation method of outdoor unit capacity from capacity tables
Equation for outdoor unit capacity calculation: Y = (Y
NOTE: Refer to
"Cooling capacity table (Outdoor unit)"
using values of X
• Calculation example of 6 Ton outdoor units: AOU72RLAVL
Total rated
capacity of
indoor unit
93.6 (130%)
X
86.4 (120%)
X
Capacity ratio of indoor units to outdoor unit (%)
Capacity of outdoor units (kBtu/h)
Y = (87.4 - 85.6)/(130 - 120) × (123.6 - 120) + 85.6 = 86.2 kBtu/h
1-3. Capacity calculation method
y
(X , Y )
Capacity ratio of indoor units to outdoor unit, X (%)
and X
.
1
2
Cooling capacity at rated condition: 72 kBtu/h (6 ton)
Outdoor
temperature
68°FDB/59°FWB
°FDB
TC
IP
5
59.6
3.11
95
59.6
4.29
115
59.6
6.68
5
55.1
2.91
95
55.1
3.98
115
55.1
5.94
(X , Y )
(X, Y)
- Y
)/(X
- X
) × (X - X
2
1
2
1
on page 02-54 to find values of Y
Indoor temperature
80°FDB/67°FWB
82°FDB/68°FWB
TC
IP
TC
93.6
4.58
97.9
86.3
7.21
87.4
Y
73.3
8.35
74.1
86.4
4.27
90.3
84.7
7.16
85.6
Y
72.1
8.35
72.9
X
= 120
1
Y
= 85.6
1
- (02-8) -
x
) + Y
1
1
and Y
1
86°FDB/72°FWB
90°FDB/73°FWB
IP
TC
IP
TC
4.76
108.9
5.10
110.3
7.24
91.5
7.35
92.6
8.35
77.3
8.35
78.1
4.44
106.0
5.12
107.4
7.19
89.7
7.30
90.7
8.35
76.1
8.35
76.9
X
X = 123.6
2
Y
= 87.4
Y
2
1. Model selection and capacity calculation
2
IP
5.10
7.38
8.35
5.11
7.33
8.35
= 130

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents