3-8. Signal amplifier (UTY-VSGXZ1)

If the total length of transmission cable exceeds 1,640 ft (500 m), or the number of the elements ex-
ceeds 64 units, Signal amplifier will be required.
To prevent the drop of signal level by taking distance of length or quantity of unit in VRF network with
installing Signal amplifier, signal level can be recovered.
¢ Accessory
Name and shape
Cable tie
Screw (M4 × 20 mm)
Terminal register
Dust proof bushing
Connecting wire
Installation manual
3-8. Signal amplifier (UTY-VSGXZ1)
Transmission cable length can be extended up to 11,811 ft (3,600 m) with
multiple Signal amplifier.
Up to 8 Signal amplifier (Filter mode is off) can be installed in one VRF net-
work system.
Up to 40 Signal amplifier (Filter mode is on) can be installed in one VRF
network system. (For Heat recovery system)
Q'ty
3
4
1
1
1
1
For mounting the power supply cable and transmission
cable
For mounting the Network convertor
For connecting the power supply cable
(Except in U.S.A. and Canada)
For setting the filter mode