4-4. Controller cable

RELATED LINKS
"Indoor unit type and applicable control method"
"Control device design limitation"
"Applicable parts"
in Chapter 10. OPTIONAL PARTS on page 10-18
¢ Wiring specifications
Model type
System controller
System controller lite
Touch panel controller
Central remote controller
Wired remote controller
1
(2-wire type)*
Simple remote controller
1
(2-wire type)*
Wired remote controller
(3-wire type)
Simple remote controller
(3-wire type)
External switch controller
IR receiver unit
(for All duct type)
IR receiver unit
(for Circular flow cassette
type)
IR receiver unit
(for Cassette type)
Human sensor kit
(for Circular flow cassette
type)
Remote sensor unit
Drain pump unit
*1: For maximum connectable number, refer to
(2-wire type)"
on page 06-63.
*2: Use shielded cable (locally purchased) in accordance with the regional cable standard.
CAUTION
• Install in accordance with the regional standard.
• Never bundle the power supply cable and controller cable together. Bundling these cords to-
gether will cause misoperation.
• Always ground for shielded cable both end.
• For details of specification and connection, refer to
SYSTEM on page 05-1.
• Controller might be required to connect power supply cable and transmission cable. For power
supply cable, use separate connection with other units.
4-4. Controller cable
in Chapter 5. CONTROL SYSTEM on page 05-12
Connection to
USB adapter
USB cable
Transmission cable
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
External input
Indoor unit
Connection cable
in Chapter 5. CONTROL SYSTEM on page 05-7
Wire
Size
Refer to
"Wiring specifications"
22 to 16 AWG
cable
(0.33 to 1.25 mm
22 AWG (0.33
cable
mm
22 AWG (0.33
cable
mm
22 AWG (0.33
mm
"Maximum connectable number of remote controller
"Control system"
- (06-62) -
Specification
on page 06-54
Sheathed, non-polar 2
2
)
core, twisted pair*
Sheathed PVC cable,
2
2
)
polar 3 core*
Shielded, polar 3 core
2
)
Shielded, non-polar 2
2
core, twisted pair
)
16 ft (5 m) cable
attached
33 ft (10 m) cable
attached
in Chapter 5. CONTROL
4. Wiring design
2