4-2. Central remote controller (UTY-DCGY)

External input and output functions and related components are as follows:
External input
Control input
RELATED LINKS
"External input"
on page 08-63
"External output"
on page 08-67
"Optional parts"
on page 08-68
"Function summary of controller external input/output"
¢ External input
This function performs "Emergency stop" or "All On / All Off" by using the signal to be input externally
at external input terminals.
 Input select
Use either one of Apply voltage terminal or Dry contact terminal according to the application. (Both
types of terminals cannot be used simultaneously.)
• CN6 and CN7: Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry contact
terminal CN6 and CN7.
*:
Short circuit detection resistance (R
Open circuit detection resistance (R
A twisted pair cable 22 AWG (0.33 mm
4-2. Central remote controller (UTY-DCGY)
External output
Operation status
Error status
*
Connected unit
2
) should be used. (Maximum cable length: 82 ft [25 m])
Input select
Connector
Dry contact
CN6, CN7
Apply voltage
CN11, CN12
on page 08-75
PCB
): ≤ 500 Ω
ON
): ≥ 100 kΩ
OFF
- (08-63) -
External connect kit
(Optional parts)
UTY-XWZXZ7
UTY-XWZXZ8
CN9
UTY-XWZXZA
CN7
(Green)
CN6
(White)