Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 99

Table of Contents

Advertisement

Nominal system capacity
Model name
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.7 °CDB/19.4 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35.0 °CDB/23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB/60 °FWB (21.1 °CDB/15.6 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.3 °CDB/6.1 °CWB).
– Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Electrical data is only for outdoor unit.
• *2: Refer to
"Power supply cable"
in Chapter 6. SYSTEM DESIGN on page 06-50 when selecting the circuit breaker.
• *3: Sound pressure level:
Measured values in manufacturer's anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *4: Minimum Circuit Ampacity (Calculation based on UL1995)
• *5: Maximum Circuit Breaker
• *6: When installation position of the outdoor unit is lower than the indoor unit, the operation temperature range is 23 to 115 °FDB (-5 to 46 °CDB).
• *7: The cooling operation range of 5 to 115 °FDB (-15 to 46 °CDB) is allowed only when all of the connected indoor units are higher than capacity of 18,000 Btu/h (5.3 kW).
2-1. Stand-alone
Ton
6
AOU72RLAVL
- (03-3) -
8
10
AOU96RLAVL
AOU120RLAVL
2. Specifications