4-1. Space requirement
Provide sufficient installation space for product safety.
 Single outdoor unit installation
• When the upper space is open:
When there are obstacles at the rear only.
When there are obstacles at the front only.
• When there is an obstruction in the upper space:
When there are obstacles at the rear and
above.
Max. 19 (500)
4-1. Space requirement
4 (100) or more
40 (1,000) or more
40 (1,000)
or more
4 (100) or more
- (03-8) -
When there are obstacles at the rear and
sides.
4 (80) or
more
8 (200) or more
When there are obstacles at the front and
rear.
40 (1,000) or more
When there are obstacles at the rear, sides,
and above.
4 (80)
or more
8 (200) or more
Unit: in (mm)
12 (300) or
more
4 (100) or more
Unit: in (mm)
60 (1,500)
or more
12 (300)
or more
4. Installation space