¢ Setting up each indoor unit
Setting must be performed on each indoor unit by repeating following procedures.
"Preparation"
on page 07-84
"Indoor unit function setting"
"Completion of setting mode"
Indoor unit
01
¢ Resetting the power after setting up all indoor units
NOTES:
• If the reset is not performed, function cannot be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
2-5. Indoor unit (setting by UTY-RNKU)
on page 07-84
on page 07-30
Indoor unit
Indoor unit
00
0
01
01
1
01
02
2
Wired remote
controller
Indoor unit
Indoor unit
01
13
0
01
Wired remote
Wired remote
controller
controller
- (07-86) -
Indoor unit
14
1
01
15
0
2. Function settings