4-4. Function summary of controller external input/output

¢ Controller external input function
Touch panel controller (UTY-DTGYZ1)
Dry contact/ Apply voltage
Function
Specifications
External
power supply
Central remote controller (UTY-DCGY)
Dry contact/ Apply voltage
Function
Specifications
External
power supply
*: Default setting is Edge signal. If you use Pulse signal, DIP switch 2-2 must be set to "On".
4-4. Function summary of controller external input/output
Emergency stop
All on / All off
(Ch1-K1, K2)
Terminal
Signal type
Allowable
voltage
Allowable
current
Wire size
Max. cable length
Emergency stop
All on / All off
Terminal
Signal type
Allowable
voltage
Allowable
current
Wire size
Max. cable length
Dry contact
(Screen icon)
(Screen icon)
TM201
TM201
(Ch1-K1, K2)
(Ch2-K1, K2)
CN201
CN201
CN411
CN411
Edge
Pulse *
22 AWG (0.33 mm
82 ft (25 m)
Dry contact
(Screen icon)
(Screen icon)
CN6
(Ch1: Pin 1-2)
CN6
(Pin 1-2)
CN7
(Ch2: Pin 1-2)
Edge
Pulse *
22 AWG (0.33 mm
82 ft (25 m)
- (08-75) -
Apply voltage
(Screen icon)
(Screen icon)
TM201
TM201
(Ch1-K1, K2)
(Ch1-K1, K2)
(Ch2-K1, K2)
CN201
CN201
CN412
CN412
Edge
Pulse *
DC12 V
10 mA or less
2
), Twisted
Apply voltage
(Screen icon)
(Screen icon)
CN11
(Ch1: Pin 1-3)
CN11
(Pin 1-3)
CN12
(Ch2: Pin 1-3)
Edge
Pulse *
DC 24 V
5 mA or less
2
), Twisted
4. Controller