Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 63

Table of Contents

Advertisement

¢ Model: ARUL14TLAV2
Outdoor temperature
°FDB
°FWB
-2.7
-4.0
5.0
3.2
10.4
8.6
15.8
14.0
17.0
15.0
23.0
21.2
26.6
24.8
30.2
28.4
32.0
30.2
35.6
33.8
41.0
39.2
47.0
43.0
48.2
46.0
53.6
51.1
59.0
56.3
¢ Model: ARUL18TLAV2
Outdoor temperature
°FDB
°FWB
-2.7
-4.0
5.0
3.2
10.4
8.6
15.8
14.0
17.0
15.0
23.0
21.2
26.6
24.8
30.2
28.4
32.0
30.2
35.6
33.8
41.0
39.2
47.0
43.0
48.2
46.0
53.6
51.1
59.0
56.3
3-5. Slim duct/Slim concealed floor type
61°FDB
64°FDB
68°FDB
TC
TC
8.1
8.1
9.4
9.4
10.5
10.4
10.4
11.5
11.4
11.4
11.7
11.6
11.6
12.9
12.9
12.8
13.6
13.6
13.5
14.3
14.3
14.2
14.7
14.6
14.5
15.4
15.3
15.2
16.6
16.5
16.2
17.4
17.3
16.2
18.0
17.4
16.2
18.3
17.4
16.2
18.3
17.4
16.2
61°FDB
64°FDB
68°FDB
TC
TC
10.4
10.4
10.4
12.1
12.0
12.0
13.4
13.4
13.3
14.7
14.6
14.6
15.0
14.9
14.8
16.6
16.5
16.5
17.5
17.4
17.3
18.4
18.3
18.2
18.9
18.7
18.6
19.7
19.6
19.5
21.3
21.2
20.8
22.3
22.1
20.8
23.0
22.3
20.8
23.4
22.3
20.8
23.4
22.3
20.8
- (02-41) -
Indoor temperature
70°FDB
72°FDB
TC
TC
TC
8.1
8.1
8.1
9.4
9.3
9.3
10.4
10.3
11.4
11.3
11.5
11.5
12.8
12.7
13.5
13.4
14.1
14.1
14.5
14.4
15.2
14.8
15.6
15.0
15.6
15.0
15.6
15.0
15.6
15.0
15.6
15.0
Indoor temperature
70°FDB
72°FDB
TC
TC
TC
10.3
10.3
11.9
11.9
13.3
13.2
14.6
14.5
14.8
14.8
16.4
16.3
17.3
17.2
18.1
18.1
18.5
18.5
19.4
19.0
20.0
19.2
20.0
19.2
20.0
19.2
20.0
19.2
20.0
19.2
75°FDB
79°FDB
TC
TC
8.1
8.0
9.3
9.3
10.3
10.3
11.3
11.2
11.5
11.4
12.7
12.6
13.4
12.7
13.9
12.7
13.9
12.7
13.9
12.7
14.1
12.9
14.1
12.9
14.1
12.9
14.1
12.9
14.1
12.9
75°FDB
79°FDB
TC
TC
10.3
10.3
11.9
11.9
13.2
13.2
14.4
14.4
14.7
14.6
16.3
16.2
17.2
16.3
17.9
16.3
17.9
16.3
17.9
16.3
18.0
16.5
18.0
16.5
18.0
16.5
18.0
16.5
18.0
16.5
3. Heating capacity table (Indoor unit)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents