¢ Setting list
LED105
Setting mode
code no.
Pipe length
0
0
setting
1
0
Prohibited
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
1
4
Prohibited
Switching
between batch
2
0
stop or
emergency
stop
2-1. Setting on outdoor unit PCB
LED104
Setting function
code no.
Standard
(131 to 213 ft)
0
0
(40 to 65 m)
Short
(less than 131 ft)
0
1
(less than 40 m)
Medium
(213 to 295 ft)
0
2
(65 to 90 m)
Long 1
(295 to 394 ft)
0
3
(90 to 120 m)
0
4
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Batch stop
0
1
Emergency stop
- (07-63) -
Factory
Remarks
setting
Pipe length means the length
between outdoor unit and the
nearest indoor unit.
Setting prohibited
Setting prohibited
Setting prohibited
This mode selects the pattern of
the stop function to be operated by
the external input terminal
(CN134).
Batch stop: The stop of all
indoor units connected to
same refrigerant system due
to input signal coming from
CN134.
Emergency stop: When
emergency stop is actuated,
the indoor unit does not
accept the operation
command from the remote
controller. On the other hand,
when the emergency stop is
released (no input from
CN134), the air conditioner
does not return to the original
operation until operate indoor
unit by the remote controller.
2. Function settings