• When function setting is Forced stop mode
NOTE: If it enters the Forced stop mode once, the indoor unit stops and Operation/Stop operation
by a remote controller will be restricted.
– In case of Edge input:
Function
setting
46-02
– In case of Pulse input:
Function
setting
46-02
CNA01
or
CNA02
Command
Indoorunit
Remote controller
3-2. External input
DIP switch
SET2-2: Off
CNA01 or CNA02
(Factory setting)
Ch1 input of
On
CNA01 or CNA02
Off
Emergency stop
Command
Normal
Operation
Indoor unit
Stop
Remote controller
DIP switch
CNA01 or CNA02
SET2-2: On
On
Ch1 Input
Off
On
Ch2 Input
Off
Forced stop
Normal
Operation
Stop
Channel
Connector
no.
Ch1
(EXT. IN1)
On
Channel
Connector
no.
Ch1
(EXT. IN1)
Ch2
On
- (08-15) -
Input signal
Command
Off → On
Forced stop
On → Off
Normal
On
On
Input signal
Command
Off → On
Forced stop
Off → On
Normal
On
On
3. Indoor unit

Hide quick links: