1-5. Capacity compensation coefficient
¢ Compensation coefficient of pipe length
The figures give the compensation coefficient of pipe length owing to installation position (pipe
length and height difference). Pipe length and height difference are the length and the height differ-
ence between master outdoor unit and indoor unit.
• Cooling
(ft)
164
131
98
66
33
-33
-66
-98
-131
• Heating
164
131
-33
-66
-98
-131
¢ Compensation coefficient of frosting/defrosting (Heating
operation)
To take the effects of accumulated frost and defrosting operation on heating capacity into considera-
tion, the capacity of outdoor units should be corrected by compensation coefficient shown in the ta-
ble below.
°FDB/
°FWB
Outdoor
temperature
°CDB/
-15/-16
°CWB
Compensation
0.96
coefficient
1-5. Capacity compensation coefficient
Outdoor unit (Higher)
(m)
50
40
30
20
10
0
0
33
66
98
131 164 197 230 262 295 328 361
-10
10
20
30
40
-20
-30
-40
Outdoor unit (Lower)
Outdoor unit (Higher)
(ft)
(m)
50
40
98
30
66
20
33
10
0
0
0
33
66
98
131 164 197 230 262 295 328 361
10
20
30
40
-10
-20
-30
-40
Outdoor unit (Lower)
5/3
16/14
19/18
-9/-10
-7/-8
0.94
0.92
100 110
50
60
70
80
90
50
60
70
80
90
100 110
23/21
27/25
32/30
-5/-6
-3/-4
0/-1
0.89
0.86
0.83
- (02-13) -
Pipe length (L)
(ft)
394
(m)
120
Pipe length (L)
(ft)
394
(m)
120
36/34
41/39
45/43
2/1
5/4
7/6
0.84
0.90
1.00
1. Model selection and capacity calculation