Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 607

Table of Contents

Advertisement

Setting subject
Outdoor unit
SetD SetE SetF
Indoor unit
63
Wired remote controller (2-wire)
Touch panel controller
Network convertor
Wired, simple remote controller
(3-wire)
Signal amplifier
Network convertor for LonWorks
Central remote controller
Instructions for setting the address:
• The refrigerant circuit address of the indoor units and outdoor units can be set to arbitrary
numbers in the range of 0 to 99.
• The indoor unit address can be set to arbitrary numbers in the range of 0 to 63.
• In case of 3-wire type of remote controller, set the remote controller address in the order of 0,
1, 2.....15. (Blank is not allowed.)
• In the automatic address setting of 2-wire type remote controller, the remote controller ad-
dress is set to "0" automatically.
• In the manual address setting of 2-wire type remote controller, the remote controller address
can be set to arbitrary numbers in the range of 1 to 15. (Setting to "0" is prohibited.)
• Touch panel controller address can be set to arbitrary numbers in the range of 0 to 15.
• The sum total of the Touch panel controller, Central remote controller, Network convertor for
Group remote controller, Modbus convertor, and Network convertor for LonWorks is a maxi-
mum of 16.
• For Touch panel controller, Central remote controller, Network convertor for Group remote
controller, Modbus convertor, and Network convertor for LonWorks connected in same VRF
network system, set an exclusive address on each device.
1-2. Address setting
Set
SetA
00
Set A
Refrigerant circuit address
Set D
Refrigerant circuit address
Set E
Indoor unit address
06
0
Set F
Remote controller address
Set F
Remote controller address
Set G
Controller address
Set H
Refrigerant circuit address
Set J
Dual remote control
Set K
Signal amplifier address
Set M
Convertor address
Set N
Controller address
- (07-7) -
Application
Rotary switch REF AD x10, x1
REF AD x10
REF AD x1
IU AD x10
IU AD x1
RC AD
Self: 0(Fixed)
Max. 16
For single split AC: Max. 100
Switch 2 of DIP switch 1
Max. 16
Remarks
1. System settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents