Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 818

Table of Contents

Advertisement

• CN11 and CN12: Apply voltage terminal
When a power supply must be provided at the input device you want to connect, connect to CN11
and CN12.
1
Make the power supply DC 24 V. Select a power supply capacity with an ample sur-
*
:
plus for the connected load.
Do not impress a voltage exceeding 24 V across pin 1-3.
2
*
:
3
The allowable current is DC 5 mA or less. (Recommended: DC 5 mA)
*
:
Provide a load resistance such that the current becomes DC 5 mA or less.
A twisted pair cable 22 AWG (0.33 mm
4-2. Central remote controller (UTY-DCGY)
DC power
supply 24 V
*
3
*
3
Connected unit
2
) should be used. (Maximum cable length: 82 ft [25 m])
*
1
PCB
3
CN11
(White)
- (08-64) -
1
3
1
*
2
CN12
(Green)
4. Controller